Walraven Pacifyre FPC Fire Collar
Technical Specification
- Manufacturer: Walraven
- Materials:
- Intumescent Inlay: Walraven Pacifyre IM Pro Flexible
- Metal Housing: Powder-Coated Galvanised Steel
- Foam: EPDM-based Foam Strip
- Size Range: 50mm to 160mm
- Suitable For: Combustible plastic and multi-layer pipes (PP, PVC and PE) used for rainwater, sewage, drinking water, heating and cooling, in flexible walls, rigid walls and rigid floors
- Fire Resistance: Up to EI 120 U/U
- Approvals: EN 1366-3 tested, ETA-22/0341, DoP-0761, CPR 22-0341
- Features:
- Two-part design allowing one half to be mounted first and the second connected later
- Built-in foam layer holds the collar in place on vertical pipes and provides noise insulation
- Connection hooks for quick, easy installation
- Intumescent inlay that heavily expands in the event of fire
Description
Engineered for the fire resistant sealing of combustible plastic and multi-layer pipe penetrations, this two-part fire collar offers a straightforward route to compliant installation across a wide range of building applications. The intumescent inlay expands considerably in the event of fire, closing the aperture left as the pipe softens and helping to maintain the integrity and insulation of the separating element.
A standout feature of this collar is its two-part design. One half can be mounted to the wall or ceiling first, with the second half connected later, which is particularly useful in awkward or busy service voids. On vertical floor penetrations, the built-in noise insulating foam helps hold the collar in position on the pipe, so it will not slip while you manoeuvre it into place. This same foam layer delivers acoustic insulation as a secondary benefit.
Suitable for use in flexible walls, rigid walls and rigid floors, the collar accommodates combustible pipes intended for rainwater, sewage, drinking water and heating or cooling services. It is compatible with a broad selection of pipe materials including PP, PVC and PE. With fire performance of up to EI 120 U/U, testing in accordance with EN 1366-3 and European approval under ETA-22/0341, it provides a reliable, certified solution for passive fire protection.
Key Features & Benefits
-
Easy to install: A two-part design with connection hooks makes fitting quick and uncomplicated, even in confined spaces.
-
Mount in two stages: Allows one half to be fixed to the wall or ceiling first, with the second half connected afterwards.
-
Stays in place on vertical pipes: The foam layer grips the pipe so the collar will not slip down during floor penetration installation, freeing both hands when positioning.
-
Built-in noise insulation: The integral foam strip provides acoustic benefits alongside its retention function.
-
High fire performance: Achieves fire resistance up to EI 120 U/U for dependable compartmentation.
-
Broad pipe compatibility: Suitable for combustible pipes in PP, PVC and PE.
-
Versatile applications: Approved for flexible walls, rigid walls and rigid floors.
-
Tested and approved: Tested to EN 1366-3 and certified under European approval ETA-22/0341.
Dimensions


| Product Code | Manufacturer Code | Pipe OD (D) (mm) | Inner Diameter (ID) (mm) | Outer Diameter (OD) (mm) | Height (H) (mm) | Width (W) (mm) | Depth (DtT) (mm) | Fixations Required |
| 493294 | 2122000050 | 50 | 58 | 77.6 | 30 | 83.3 | 148.5 | 2 |
| 493295 | 2122000063 | 63 | 71 | 95.6 | 30 | 139.5 | 129.1 | 4 |
| 493296 | 2122000075 | 75 | 83 | 112.2 | 40 | 139.0 | 146.8 | 4 |
| 493297 | 2122000090 | 90 | 98 | 127.6 | 40 | 157.4 | 156.8 | 4 |
| 493298 | 2122000110 | 110 | 118 | 147.6 | 40 | 166.8 | 175.5 | 4 |
| 493299 | 2122000125 | 125 | 133 | 167.6 | 60 | 199.7 | 169.1 | 4 |
| 493300 | 2122000140 | 140 | 148 | 192.4 | 60 | 220.2 | 259.0 | 6 |